Formula variables
- A is conductor area in mm2.
- K is material resistivity in ohm mm2/m.
- I is PV DC current in amperes.
- Allowed percent is the voltage-drop target used for the distance screen.
Assumptions
- The calculator rearranges the DC voltage-drop formula to solve one-way run length.
- Allowed voltage drop is entered as a percent of nominal array voltage.
- The result is a voltage-drop distance screen before product, temperature, installation, and protection checks.
- This calculator does not choose PV wire, protection, disconnects, temperature treatment, wiring method, or installation approval.
Examples
600 V PV DC run. At 600 V, 20 A, copper 6 AWG, and a 3 percent drop target, the maximum one-way distance estimates about 347.1 m.
Tighter drop target. A 1 percent target shortens the allowable run and may require a larger conductor or different array/inverter layout.