Formula variables
- PF is the power factor entered for the load.
- V is the selected nominal voltage.
- kW is real power and kVA is apparent power.
- Three-phase current uses line-to-line voltage.
Assumptions
- The calculator treats voltage as nominal and line current as the current for the selected phase system.
- Power factor is required to convert between real power and apparent power.
- The result is a formula conversion, not a conductor, breaker, transformer, generator, service, or code-compliance selection.
- Use nameplate, measured, utility, or engineering data where available before using a planning estimate.
Examples
600 V three-phase load. A 25 kW load at 0.90 PF on 600 V three-phase converts to about 27.78 kVA and 26.73 A.
Fast table handoff. Use this solver for a project-specific value, then use the kVA/amps and power-factor tables for quick sanity checks.