Formula variables
- Transformer kVA is the transformer rating entered by the user.
- Secondary voltage is the transformer secondary nominal voltage.
- Impedance percent is the transformer nameplate impedance value.
- Available current is a transformer-only approximation before system fault-current study adjustments.
Assumptions
- The estimate uses transformer full-load current divided by impedance in per-unit.
- The result is transformer-only available current at the secondary terminals.
- Utility source impedance, motor contribution, conductor impedance, and protective-device clearing are not included.
- Use transformer nameplate impedance and project fault-current study values for equipment rating review.
Examples
75 kVA at 600 V. A 75 kVA three-phase transformer at 600 V with 5.75 percent impedance gives about 72.2 A full-load current and about 1.26 kA transformer-only short-circuit current.
Study boundary. If equipment rating is being selected, include utility source impedance, conductor impedance, motor contribution, and the actual protective-device arrangement.