Reference boundary

Equipment label mapping only. It does not choose equipment, calculate fault current, confirm series ratings, or approve substitutions.

Reference table

Map common equipment types to the short-circuit rating label users should look for first.

Reference basis summarizes common rating-label ownership from manufacturer breaker, fuse, panelboard, switchboard, and control-panel literature.
Equipment typeRating labelLabel ownerReview useBoundary
Molded-case circuit breakerAIC / interrupting ratingbreaker labelcompare marked interrupting rating with available fault currentlabel mapping only; do not infer a rating where the equipment marking does not state one
FuseInterrupting ratingfuse labelcompare marked interrupting rating with available fault currentlabel mapping only; do not infer a rating where the equipment marking does not state one
PanelboardShort-circuit current rating or series-rated labelpanelboard label and directoryconfirm the panel and installed breakers match the rating labellabel mapping only; do not infer a rating where the equipment marking does not state one
SwitchboardShort-circuit current ratingswitchboard nameplateconfirm the assembly rating and installed protective deviceslabel mapping only; do not infer a rating where the equipment marking does not state one
Industrial control panelSCCRcontrol panel nameplatecompare assembly SCCR with available fault current at the panellabel mapping only; do not infer a rating where the equipment marking does not state one
Disconnect switchWithstand or short-circuit rating with fuse/breaker conditionsswitch label and instructionsconfirm required protective-device pairinglabel mapping only; do not infer a rating where the equipment marking does not state one
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.