Reference boundary

Full-load current arithmetic only. It does not set primary or secondary protection.

Reference table

Convert common single-phase transformer kVA ratings to full-load current at 120, 240, and 600 V.

Formula basis: single-phase full-load amps = kVA x 1000 / voltage.
Transformer kVA120 V A240 V A600 V A
18.34.21.7
32512.55
541.720.88.3
1083.341.716.7
1512562.525
25208.3104.241.7
37.5312.5156.362.5
50416.7208.383.3
75625312.5125
100833.3416.7166.7
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.