Scope

Motor current estimate only. Motor nameplate current, voltage, efficiency, power factor, duty, and product data govern field application.

Lookup table

Estimate single-phase motor full-load current at common Canadian utilization voltages.

Scroll sideways to keep row labels aligned with hidden columns.

Formula basis: amps = hp x 746 / (volts x efficiency x power factor), using rounded assumptions.
Motor hpVoltageEstimated FLA (A)AssumptionBoundary
0.25120460% efficiency, 0.65 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
0.5120765% efficiency, 0.68 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
0.751209.868% efficiency, 0.7 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
11201272% efficiency, 0.72 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
1240672% efficiency, 0.72 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
1.52408.375% efficiency, 0.75 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
224010.278% efficiency, 0.78 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
324014.680% efficiency, 0.8 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
524022.684% efficiency, 0.82 PFformula estimate only; motor nameplate FLA and manufacturer data govern field application
Notes
  • Check table values for preliminary lookup and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.