PVC Conduit Thermal Expansion Table
PVC Conduit Thermal Expansion Table reference with assumptions and boundary notes.
Reference boundary
Thermal expansion arithmetic only. Manufacturer expansion-joint instructions, conduit type, supports, and field conditions govern installation details.
Reference table
Estimate PVC conduit length change from run length and temperature change using a rounded expansion coefficient.
| Run length (m) | Temperature change (C) | Estimated movement (mm) | Estimated movement (in) | Boundary |
|---|---|---|---|---|
| 10 | 20 | 10.4 | 0.41 | Manufacturer expansion-joint placement instructions still govern |
| 10 | 40 | 20.8 | 0.82 | Manufacturer expansion-joint placement instructions still govern |
| 30 | 20 | 31.2 | 1.23 | Manufacturer expansion-joint placement instructions still govern |
| 30 | 40 | 62.4 | 2.46 | Manufacturer expansion-joint placement instructions still govern |
| 50 | 40 | 104 | 4.09 | Manufacturer expansion-joint placement instructions still govern |
| 50 | 60 | 156 | 6.14 | Manufacturer expansion-joint placement instructions still govern |
Use notes
- Use this table for preliminary reference and arithmetic checks only.
- Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.