Scope

Locked-rotor current arithmetic only. Motor nameplate data, manufacturer curves, starter settings, voltage dip study, and qualified review govern field application.

Lookup table

Estimate locked-rotor current from horsepower, voltage, phase, and a selected code-letter kVA-per-hp midpoint.

Scroll sideways to keep row labels aligned with hidden columns.

Formula basis: estimated three-phase LRA = hp x selected locked-rotor kVA per hp x 1000 / (sqrt(3) x volts).
Motor hpVoltageCode letterkVA/hp midpointEstimated LRA (A)Boundary
5600F4.7523estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
10600G5.351estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
25600H6.3152estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
50600J7.5361estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
100600K8.5818estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
10208G5.3147estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
25208H6.3437estimate only; use the actual motor nameplate LRA or manufacturer starting data when available
Notes
  • Check table values for preliminary lookup and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.