Motor current estimate only. Motor nameplate current, service factor, efficiency, power factor, voltage, and product data govern field use.

Reference table

Estimate three-phase motor full-load current at 600 V from horsepower, efficiency, and power-factor assumptions.

Formula basis: amps = hp x 746 / (sqrt(3) x 600 V x efficiency x power factor), using rounded assumptions.
Motor hpEstimated FLA at 600 VEfficiency assumptionPF assumptionBoundary
11.182%0.8formula estimate only; motor nameplate FLA governs field use
22.282%0.8formula estimate only; motor nameplate FLA governs field use
33.382%0.8formula estimate only; motor nameplate FLA governs field use
54.888%0.85formula estimate only; motor nameplate FLA governs field use
7.57.288%0.85formula estimate only; motor nameplate FLA governs field use
109.688%0.85formula estimate only; motor nameplate FLA governs field use
1513.892%0.85formula estimate only; motor nameplate FLA governs field use
2018.492%0.85formula estimate only; motor nameplate FLA governs field use
2522.992%0.85formula estimate only; motor nameplate FLA governs field use
3027.592%0.85formula estimate only; motor nameplate FLA governs field use
4036.792%0.85formula estimate only; motor nameplate FLA governs field use
5045.992%0.85formula estimate only; motor nameplate FLA governs field use
7568.892%0.85formula estimate only; motor nameplate FLA governs field use
10091.892%0.85formula estimate only; motor nameplate FLA governs field use
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.