Table
Duct Heater Line Current Multipliers
Duct Heater Line Current Multipliers reference with assumptions and boundary notes.
Reference boundary
Multiplier reference only. Confirm heater nameplate voltage, phase, steps, and controls.
Reference table
Use amps-per-kW multipliers for duct heater current estimates by voltage and phase.
| Voltage and phase | Amps per kW | Formula | Example |
|---|---|---|---|
| 120 V 1-phase | 8.33 | 1000 / 120 | 5 kW x 8.33 = 41.7 A |
| 208 V 1-phase | 4.81 | 1000 / 208 | 5 kW x 4.81 = 24.0 A |
| 240 V 1-phase | 4.17 | 1000 / 240 | 5 kW x 4.17 = 20.8 A |
| 600 V 3-phase | 0.96 | 1000 / (sqrt(3) x 600) | 30 kW x 0.96 = 28.9 A |
Use notes
- Use this table for preliminary reference and arithmetic checks only.
- Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.