Table
Duct Heater Line Current Multipliers
Duct Heater Line Current Multipliers lookup table with assumptions and boundary notes.
Scope
Multiplier planning only. Confirm heater nameplate voltage, phase, steps, and controls.
Lookup table
Use amps-per-kW multipliers for duct heater current estimates by voltage and phase.
Scroll sideways to keep row labels aligned with hidden columns.
| Voltage and phase | Amps per kW | Formula | Example |
|---|---|---|---|
| 120 V 1-phase | 8.33 | 1000 / 120 | 5 kW x 8.33 = 41.7 A |
| 208 V 1-phase | 4.81 | 1000 / 208 | 5 kW x 4.81 = 24.0 A |
| 240 V 1-phase | 4.17 | 1000 / 240 | 5 kW x 4.17 = 20.8 A |
| 600 V 3-phase | 0.96 | 1000 / (sqrt(3) x 600) | 30 kW x 0.96 = 28.9 A |
Notes
- Check table values for preliminary lookup and arithmetic checks only.
- Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.