Scope

Geometry planning only. Actual field layout depends on bender markings, raceway type, and installer tolerance.

Lookup table

Estimate conduit shrink per unit of offset for common offset bend angles.

Scroll sideways to keep row labels aligned with hidden columns.

Formula basis: shrink per unit offset = tan(angle / 2).
Bend angleShrink per unit offsetField approximationUse
100.087about 1/16 per unit offsetShrink = offset depth x shrink constant
22.50.199about 3/16 per unit offsetShrink = offset depth x shrink constant
300.268about 1/4 per unit offsetShrink = offset depth x shrink constant
450.414about 3/8 per unit offsetShrink = offset depth x shrink constant
600.577about 1/2 per unit offsetShrink = offset depth x shrink constant
Notes
  • Check table values for preliminary lookup and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.