Reference boundary

Formula example only. Cable manufacturer limits, raceway condition, lubricant, bend sequence, pulling setup, and qualified review govern pull acceptance.

Reference table

Show basic pulling-tension and sidewall-pressure arithmetic relationships for preliminary pull planning.

Formula basis: straight-pull tension = weight x length x friction coefficient; sidewall pressure = tension / bend radius.
ScenarioCable weight (kg/m)Straight length (m)Friction coefficientEstimated tension (N)Bend radius (m)Sidewall pressure (N/m)
Straight pull example21000.59810.61634
Longer pull example21500.514710.62452
Lower friction example21000.356860.61144
Larger bend radius example21000.59810.91090
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.