Formula variables
- Current probe distance is the entered distance from the electrode under test.
- Voltage probe percent sets the voltage-probe placement along that distance.
- Electrode offset is an optional extra lead allowance.
- Total lead length is a setup planning estimate.
Assumptions
- The calculator only places probes along the entered test line.
- The voltage-probe percent is entered by the user, with 62 percent as the default shortcut.
- Soil conditions, electrode geometry, and instrument method can invalidate a simple spacing layout.
- This calculator does not set pass or fail targets, approve grounding systems, or replace instrument instructions.
Examples
62 percent setup. With a 30 m current-probe distance, a 62 percent voltage-probe point is 18.6 m from the electrode.
Test workflow. Use instrument instructions and site conditions before relying on a simplified probe layout.