Formula variables
- Generator kW is real power.
- Power factor converts kW to kVA.
- V is selected single-phase voltage.
- Current is the steady-state estimate before surge and receptacle limits.
Assumptions
- The conversion uses single-phase apparent-power arithmetic.
- Power factor is editable because generator kW and kVA ratings may differ.
- Generator receptacle current limits, breaker labels, voltage dip, and surge loads can override the simple conversion.
- This calculator does not account for surge loads, voltage dip, generator receptacle ratings, transfer equipment, fuel derating, or standby-system design.
Examples
5 kW at 240 V. A 5 kW single-phase generator at 240 V and PF 1.00 estimates about 20.8 A.
10 kW at PF 0.80. At 10 kW and PF 0.80, apparent power is 12.5 kVA and 240 V current estimates about 52.1 A.